Temperature Transmitter FRC

Product Options
Indicator
Housing
Hazardous Area Cert
Conduit Con

Temperature Transmitter FRC

New

Fuji Electric FRC is a programmable universal input two wire temperature transmitter suitable for head or field mounting. Available with ATEX Explosion-proof, Intrinsically Safe certification and Stainless Steel enclosure.

More details

Fuji Electric FRC is a programmable - universal input - two wire temperature transmitter suitable for head or field mounting. It is available with ATEX Explosion-proof, Intrinsically Safe certification and Stainless Steel enclosure.

Fuji Electric FRC Temperature Transmitter


Features:

  • Universal input: mV, V, T/C and RTD
  • High accuracy
  • HART communication
  • Intrinsically safe and explosion-proof approval
  • CE marking (conforms to ATEX and EMC)
  • Protection: NEMA4X IP66/IP67
  • Optional stainless steel enclosure
  • Programming via hand-held communicator or via PC
  • Self diagnostics
  • Input-output isolated

    Degree of protection : NEMA 4X, IP66/IP67
    Wiring conduit : See “Model & Suffix Code”.
    Electrical connection : M3.5 screw terminals (torque 0.8 N·m)

    Materials
    Transmitter housing : Flame-resistant resin (black)
    Screw terminals : Nickel-plated brass

    Enclosure :
    Diecast aluminium standard (polyurethane coated)
    or stainless steel casting (equivalent to type 316,
    epoxy resin coated).

    Enclosure color :
    Body : Silver
    Cover : Blue (equivalent to Munsell GPB3.5/10.5)
    Silver for stainless steel

    Mounting bracket assembly :
    Stainless steel 304
    Applicable pipe :
    1” 1/2 min.; 2” max.

    Isolation :
    Input to output to outdoor enclosure

    User-configurable parameters :
    · Input sensor type
    · Number of wires (RTD)
    · Input range
    · Output range (via HART® only)
    · Output calibration
    · HART communication mode
    · HART network mode

    Burnout (T/C & RTD) :
    Upscale, downscale or no burnout selectable
    (standard: upscale);
    Also detects wire breakdown and overrange input
    exceeding the electrical design limit for DC input.

    Cold junction compensation (T/C) :
    CJC sensor incorporated

    Damping time :
    0 to 30 sec. (standard : 0)

    Measurement type Temperature